The EN 16005, is a harmonised European Standard, which defines Requirements and Test Methods for safety in use of powered pedestrian doors.
The Standard defines the Essential Health and Safety Requirements (EHSRs) and the “State of the Art” safeguarding. For new doors installed, the EHSRs and safeguarding become the minimum requirement to ensure the safety of employees and users under the 2006/42/EC Machinery Directive (MD) in the EU and the Supply of Machinery (Safety) Regulation 2008 as amended 2010(SMR08) for the UK.
National and European Standards are not legally binding, however if they are harmonised or designated, for new machines they become what is deemed as the minimum safety requirement to comply to the machinery laws; However, the system must be risk assessed to ensure it is safe for all anticipated users, this is where the BS 7036:2026 Risk assessment- risk reduction- code of practice, assists.
For existing machines the current standard is seen as “best practice.” Under H&S Laws the owner/occupier must do what is reasonable and practicable to comply to the latest standard. This will mean the owner/occupier are required to carry out a documented risk assessment, this should determine if they could comply to the latest standard with reasonable and practicable adjustments, if not then the reason why they can't along with any mitigating measures that could be put in place to reduce the risk. These safety standards (EN 16005/BS 7036) are always referred to as best practice in courts where accidents and injuries from use of Powered Pedestrian Doors have occurred.
Existing machines that require significant changes, an example would be a different model of drive unit, these are classed as new machines.
For all systems the safety level must always be risk assessed to ensure it is safe for all users.
In short - YES
There are 2 requirements that are set out in the EN 16005:
Maintenance & Inspection, they are often carried out at the same time by an Authorized Technician (see BS 7036:2026) Maintenance is like a service where inspection is more like an MOT.
Excerpt from BS 7036:2026: WARNING. A lack of maintenance can lead to unsafe operation.
Under the Machinery Directive (EU) or the Supply of Machinery Safety Regulations (UK) Powered Pedestrian Doors must be operated safely, safe for employees and safe for other users. The doors therefore need to be maintained in accordance with the guidance from the manufacturer, this should state what needs to be carried out and the frequency. However the law does not specifically state that the doors need to be serviced but failing to maintain them so they are safe in use would lead to a prosecution if there was an injury.
The law for servicing equipment is dependent on which country or devolved government you are in, however they all have similar content, here is an example for England and Wales:
Regulation 5 of the Workplace (Health, Safety and Welfare) Regulations 1992), state. Extract: "...... the equipment devices and systems to which this regulation applies shall be subject to a suitable system of maintenance."
Regulation 5 of the Provision & Use of Work Equipment Regulations 1998 (PUWER)
Extract A: "Every employer should ensure that work equipment is maintained in an efficient state, in efficient working order and in good repair."
Extract B: "Every employer should ensure that where any machinery has a maintenance log, the log is kept up to date."
The Machinery Directive 2006/42/EC (MD) is the EU directive that ensures all machines supplied to the market are safe. It will be replaces with the Machinery Regulation (MR)EU 2023/1230 on 20/1/2027.
The MD/MR does not apply to GB post Brexit, however it will be enforced within NI due to the Northern Ireland Protocol.
The Supply of Machinery (Safety) Regulation 2008 amended 2011 (SMR08) is the UK's domestic legislation to enforce the same requirements of the MD.
The UK government have announced that they intend to bring the SMR08 inline with the new EU machinery regulation when parliamentary time allows.
EN 16005 took effect from April 2013 and applies to new installations installed after that date. This has been superseded by EN 16005:2023+A1:2024
EN 16005:2023+A1:2024 should be read in conjunction with the BS 7036:2026
BS 7036:1996 parts 1-5 could be applied to existing installations fitted prior to April 2013 as long as they have not undergone any significant changes; However the client should always comply to the latest standards when reasonable and practicable.
EN 16005 is the European standard which gives guidance on safety in use and test methods for Powered Pedestrian doorsets. It is the industry guidance document to help companies meet the requirements of the Machinery Directive or the Supply of Machinery Regulations, it forms part of the CE/UKCA/UKNI Marking process. The document gives practical advice on safety systems and best practice ways for ensuring Powered Pedestrian doors are installed with acceptable levels of safety for users. The standard is a minimum level of safety allowed for new installations
ADSA have collaborated with DHF to developed the Entrance System Alliance (ESA), an NVQ assessment centre, it covers the installation and servicing of powered doors. This is designed for people already in the trade that need to be qualified. The NVQ is administered through the ESA who have their own assessing capabilities. This NVQ qualification proves competence and is part of the process towards obtaining a ADSA Skilled worker card as part of the Construction Skills Certification Scheme (CSCS), which is a requirement of the Major Contractor Group to working on their construction sites. follow this link for more information: Homepage | ESA
Abingdon and Whitney college in partnership with ADSA provide an apprenticeship for Powered Pedestrian Doors, unlike the NVQ this also provides full training, the delegates will have 20% off the job training, most of this will be a week’s block release every 5-6 weeks, at the moment this will be in Cowley, Oxford, England, other centres may be available in due course. Follow this link https://abingdon-witney.ac.uk/courses/powered-pedestrian-door-installer-service-engineer-level-2-apprenticeship-2177105 or contact Automatic Door Suppliers Association for more information
For the authorised technicians tests, ADSA recommend a field test box of 700 x 300 x 200mm with black and grey surfaces and for hinge protection with ESPE it should be a 20mm tube with 8mm inset.
The occupiers tests require a box 700 x 300 x 200mm.
For ADSA member please see the technical download and bulletin on the ADSA academy.
It is essential that the occupier carries out frequent safety checks (at least weekly) on Powered Pedestrian Doors, Please see the videos on how to carry these out for swing or side doors on the Education Tab of ADSA website.
https://adsa.org.uk/education/occupier-safety-check-videos/
These do not replace the inspection and Maintenance required by the Authorized door technician.
The standards are available to be purchased from the national setting body of your country.
UK - BSI, BSI Knowledge - Shop BSI Standards https://knowledge.bsigroup.com/
ADSA Members can purchase BS standards at reduced rates- please email technical@adsa.org.uk to request a standards ordering form.
Ireland - NSAI https://www.nsai.ie/
ADSA believes that its work on Technical Standards is paramount. ADSA has representative on Technical Standards committees including;
The technician has a legal requirement to ensure the door system is safe when they leave site. If a door is not safe and is likely to harm someone then the technician should stop the door from operating, this could be i.e. switch the door to hold open or off. The technician should then complete a door warning notice (for members available on the ADSA Academy) advise the customer why the system is unsafe, how it can be made safe and they should not put the system back in use until the safety issues have been resolved.
The reason for the system being unsafe should be recorded on the engineers signed worksheet. The service company should then provide a written quotation to the customer asap ( ADSA would recommend within 2 weeks) and the works needed to make it safe so they have an option on how to proceed. The customer is relying on the service company to provide best practice advice as the expert.
When components or products are replaced during maintenance, repair or upgrading, it has to be ensured as a minimum, that the safety, reliability, functionality, classification and durability level of the doors is kept. In other words: keep the performance and don’t add hazards or increase risks.
Use of original components is preferred, but if non original or ‘look alike’ components are used which may affect the declared characteristics, or safety level, the evaluation of conformity shall be reviewed for applicability by a qualified service provider.
The Service provider is obliged to offer the customer the state-of-the-art safety level, i.e. to latest standard.
If the repair only exchanges components with the same characteristics (=repair) but: If the whole electrical drive system is replace with a different model then this is a new machine (Modernisation kit)
No functionalities are changed. The safety level has to be at least kept at present level. The safety level may never be reduced.
If the kit makes the doorset a new machine
This is the case where the functionality for the user is changed in products. Sensors are replaced and the machine is brought up to compliance with the state-of-the art, i.e. EN 16005.
In these circumstances where engineers conduct work for you but are not employed by your company, as a minimum they will need to sign up with ADSA as a Sole Trader. Please refer to the becoming a member page on the website.
This is correct and is covered by clause 5.8.2 of BS EN 16005:2023
BS7036:2026 Power operated pedestrian doorsets, entrance control equipment and manually operated revolving doorsets - Safety in use, risk assessment and risk reduction - Code of practice
It is the most significant revision of the UK's principal Code of Practice for pedestrian entrance safety in more than a decade
It is a British standard that assist in carrying out the legal requirement of a documented risk assessment for the door systems in scope of the standard.
It introduces a stronger focus on vulnerable users, accessibility, competence, signage and risk assessment, while supporting the application of BS EN 16005 and BS EN 17352.
It should not be confused with previous BS 7036:1988/1996 standards which were replaced with the EN 16005 in 2012.
It is intended to be used by suppliers, installers, specifiers, occupiers, property owners and duty holders. It is also intended to be used by designers of the application into which the doorset is to be installed.
The industry now has a clear guidance document which will be very useful for member companies, salespeople, estimators, surveyors and their clients.
ADSA would always recommend that anyone involved in the supply & installation of door automation products has a good knowledge of the regulations and relevant standards including BS EN 16005 & other related standards. The best way of both proving & acquiring the required knowledge is by being trained to the relevant standards & taking the exam offered by the ADSA.
ADSA offer a 2-day training course & exam to members details of which can be seen on this website.
With regard to the installation being in a domestic premises it would still fall under BS EN 16005 & related legislation, even though it would be someone’s home, an install or maintenance technician can face prosecution if the system is left unsafe.
We would as always recommend a full “risk assessment” is carried out before any installation in line with the guidelines of EN 16005 & BS 7036:2026.
The door would fall under BS 7036 1996 it is not a mandatory requirement to monitor the safety devices but it does state where practical it should.
All systems should be upgraded to the latest standard when reasonable and practicable, if this is not the case then the system can continue under the previous standard.
If not practical, leave the monitoring disconnected on the replacement sensors as it would not downgrade the safety of the unit merely maintain the existing level.
In this case, the client should carry out more frequent occupier safety checks as a mitigating measure to ensure the continued safe operation of the system.
Unfortunately, “safety in use” takes precedence over all else including advertising. Powered pedestrian doors are classified as machines and therefore must adhere to the Supply of Machinery Regulation 2008 and the Machineries Directive/Regulation.
As part of the risk assessment and where powered pedestrian doors are used, warning signage along with safety sensors and other protective devices and guards should be fitted. The inclusion of warning signage is to make users aware that residual risks are present and to help reduce the number of accidents associated with powered pedestrian doors.
ADSA represents the majority of the Powered pedestrian door industry and as part of its best practice ethos, ADSA recommends that the signage as denoted within BS 7036:2026 is applied. For your reference, in the UK, the particular signage recommended for powered pedestrian doors came about as a result of consultation with organisations representing the partially sighted and by following the content within the Supply of Machinery Act. The signage has been designed to make users (particularly partially sighted persons) aware that the doors are automatic and where keep clear signage is applied, to keep clear of the area where the automatic door operates, there have been additional signage and guidance added to the BS 7036:2026, this includes, Powered Door Push Button to Open, access Controlled powered Door and Supervision of Children signs.
The signage should be placed between 1300 -1600mm from the Finished floor level.
Extract from Supply of Machinery (safety) Regulation 2008 (please note that full document is available free online and should be read in its entirety)
1.7. INFORMATION
1.7.1. Information and warnings on the machinery
Information and warnings on the machinery should preferably be provided in the form of readily understandable symbols or pictograms. Any written or verbal information and warnings must be expressed in an official Community language or languages, which may be determined in accordance with the Treaty or the EEA Agreement by the EEA state in which the machinery is placed on the market and/or put into service and may be accompanied, on request, by versions in any other official Community language or languages understood by the operators.
In conclusion, if the end user decides to remove the signage, they must be made aware of the residual risks and acknowledge that they understand the possible implications. Irrespective of the end user’s acknowledgement, I should also point out that the responsible person or persons bringing the machine (in this case, the automatic door) into service has the responsibility to ensure that the system meets the requirements of the relevant standards (EN 16005:2023+A1:2024, BS 7036:2026 and where applicable BS 7036:1996) and complies with the requirements of the Supply of Machinery Act. Where a reportable injury occurs with a powered pedestrian door, the Health and Safety Executive (HSE) will be involved. HSE will refer the Standards and regulations/Acts mentioned above and determine if due diligence has been carried out and may call upon an expert to verify whether the system complies.
5.4.1 Materials
There shall be no sharp edges and glazing shall not form sharp splinters if broken.
Toughened glass in accordance with EN 12150-1:2015+A1:2019 and laminated glass in accordance with EN ISO 12543-1:2021 and EN ISO 12543-2:2021 are examples of suitable glazing materials.
Plain float glass (according to EN 572-2:2012) and wired glass are not suitable for this application due to the risk of serious injury upon breaking.
If glass is protected from breaking by thick film etc, it could be deemed as compliant to machinery law but great care is needed to ensure it does not effect fire integrity if a fire door.
There is also a risk assessment and reduction standard BS 7036:2026, this also states:
Glass should be appropriately marked, or incorporate features to make its presence apparent, in accordance with BS 8300-2.
Where other materials are used as an alternative to glass, these should not expose sharp edges when in good condition or when deformed or broken.
NOTE Guidance is given in HSE publication L24 [1]